Dust Emission Limits from 2028: Is Your Biomass Heating Plant Ready?
Updated: Oct 9

From 1 January 2028, new dust emission requirements will apply to many existing wood-fired and biomass heating plants in Germany. These requirements are set out in the 44th Federal Immission Control Ordinance (44. BImSchV), which regulates emissions from medium combustion plants.
However, this does not necessarily mean that an existing heating plant needs to be replaced. If it already meets the applicable emission limit, no additional dust filtration measures may be required. If dust emissions exceed the permitted level, retrofitting an Electrostatic Filter can offer an alternative to replacing the boiler.
The key is to assess your plant first, then decide on the next steps.
What Changes on 1 January 2028?
The new requirements primarily affect existing plants with a rated thermal input of 1 MW to less than 5 MW that use solid biomass fuels. For certain plants below 5 MW burning untreated, natural wood, a total dust emission limit of 35 mg/m³ at 6% reference oxygen (O₂) applies. The ordinance also includes a special provision for certain existing plants that were already equipped with a filtration system or an electrostatic dust collection system on 20 June 2019. For these plants, where untreated, natural wood is used as fuel and the rated thermal input is below 5 MW, the total dust emission limit is 50 mg/m³ at 6% reference oxygen (O₂). However, the applicable emission limit depends on more than just the plant's rated thermal input. The fuel used and the specific plant configuration also play an important role.
How Does the Fuel Type Affect the Requirements?
The dust emission limits of 35 and 50 mg/m³ mentioned above apply to certain plants burning untreated, natural wood. Examples include untreated Wood Chips, sawdust and other natural wood residues. Under certain conditions, Category A I waste wood may also be classified as untreated, natural wood.
Other categories of waste wood require a more detailed assessment:
A I: Untreated or mechanically processed waste wood that is virtually free from contamination.
A II: Glued, painted, coated or varnished waste wood without organohalogen compounds in its coatings and without wood preservatives.
A III: Waste wood containing organohalogen compounds in its coatings but no wood preservatives.
A IV: Waste wood treated with wood preservatives, as well as other similarly contaminated wood waste.
These categories are defined under Germany's Waste Wood Ordinance. The applicable emission requirements depend on the actual composition of the fuel and the characteristics of the plant.
Different or additional requirements may apply to Category A II to A IV waste wood and other biomass fuels. In certain cases, other regulations may also be relevant. The first step is therefore to assess the fuel and the existing plant before determining which emission limit applies.
Retrofit Instead of Replace
An Electrostatic Filter can be integrated into an existing Flue Gas System to remove dust particles from the Flue Gas. This allows the existing plant to remain in operation while significantly reducing particulate emissions. Retrofitting can be particularly attractive when the existing boiler is still in good technical condition but no longer meets the applicable dust emission requirements. Rather than replacing the entire heating plant, the upgrade targets the area where action is actually needed: dust removal.
Whether retrofitting is the right solution depends on the plant's current emission levels, system configuration and installation conditions.
Finding the Right Retrofit Solution with Meisterfilter
Meisterfilter develops and manufactures Electrostatic Filters for wood-fired and biomass heating plants. Our solutions are generally suitable for retrofitting boilers from a wide range of manufacturers and can be flexibly integrated into existing plants.
Thanks to their modular design, our Filter Systems can be adapted to different thermal capacities, plant configurations and space constraints. We work closely with plant operators to assess their existing plants and identify the most suitable retrofit solution.
Assess Your Plant Now, Avoid Last-Minute Pressure
Affected plant operators must ensure their plants comply with the relevant requirements by 1 January 2028. However, technical assessments, planning and retrofit installation all take time. Taking action early allows operators to plan any necessary upgrades more effectively and, where possible, coordinate installation work with scheduled maintenance or planned shutdowns.
Will your biomass heating plant be ready for 2028? We can help you assess whether retrofitting an Electrostatic Filter is the right solution for your existing plant.